Bi: Or Logic Operation Inputs / Or Inputs; Co/Bo: Or Logic Operation Result / Or Result; Co: Fixed Value 1 [%] / Fixed Value 1 [%]; Co: Fixed Value 2 [%] / Fixed Value 2 [%] - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p2816[0...1]

BI: OR logic operation inputs / OR inputs

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal sources for the inputs of the OR logic operation.
Dependency:
Refer to: r2817
Note:
[0]: OR logic operation, input 1 --> the result is displayed in r2817.0.
[1]: OR logic operation, input 2 --> the result is displayed in r2817.0.
r2817.0

CO/BO: OR logic operation result / OR result

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Functions
Not for motor type: -
Min
-
Description:
Displays the result of the OR logic operation.
Bit field:
Bit
00
Dependency:
Refer to: p2816
p2900[0...n]

CO: Fixed value 1 [%] / Fixed value 1 [%]

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Free function blocks
Not for motor type: -
Min
-10000.00 [%]
Description:
Setting and connector output for a fixed percentage value.
Dependency:
Refer to: p2901, r2902, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the main setpoint)
p2901[0...n]

CO: Fixed value 2 [%] / Fixed value 2 [%]

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Free function blocks
Not for motor type: -
Min
-10000.00 [%]
Description:
Setting and connector output for a fixed percentage value.
Dependency:
Refer to: p2900, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
550
Signal name
OR logic operation result
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: PERCENT
Max
10000.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: PERCENT
Max
10000.00 [%]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 2634
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2634
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
Access level: 3
Func. diagram: 1021
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 3
Func. diagram: 1021
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
SINAMICS G130/G150
FP
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents