p9556

SI Motion STOP A delay time (Control Unit) / SI Mtn IL t_del CU

VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the delay time for STOP A after STOP B.
In the case of encoderless motion monitoring functions with safe brake ramp monitoring (p9506 = 1) and the OFF3
ramp enabled at the same time (p9507.3 = 0), the parameter has no effect.
Dependency:
Refer to: p9560
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
p9557

SI Motion STO test time (Control Unit) / SI Mtn IL t_test

VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the time after which STO must be active when initiating the test stop.
Note:
A change only becomes effective after a POWER ON.
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
p9558
SI Motion acceptance test mode time limit (Control Unit) / SI Mtn acc t CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
5000.00 [ms]
Description:
Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
p9559
SI Motion forced checking procedure timer (Control Unit) / SI Mtn dyn timer
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [h]
Description:
Sets the time interval for carrying out the forced checking procedure and testing the safety motion monitoring
functions integrated in the drives.
Within the parameterized time, the safety functions must have been tested at least once (including de-selection of the
"STO" function).
This monitoring time is reset each time the test is carried out.
The signal source to initiate the forced checking procedure is set in p9705.
Dependency:
Refer to: p9705
Note:
STO: Safe Torque Off
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3600000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
10000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
9000.00 [h]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
40000.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
8.00 [h]
893