Topology Comparison Component Replacement / Topo_Cmpr Replace; Target Topology Accept Additional Components / Add Comp Accept - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

3:
99:
Dependency:
Refer to: p9907
Note:
The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9908 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9908 = 1: Component type, Order No.
p9908 = 2: Component type
p9908 = 3: Component class (e.g. Sensor Module or Motor Module)
p9909

Topology comparison component replacement / Topo_cmpr replace

CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Unsigned8
CU_G150_DP,
P-Group: Topology
CU_G150_PN
Not for motor type: -
Min
0
Description:
For p9909 = 1, the serial number and the hardware version of the new replaced component is automatically
transferred from the actual topology into the target topology and then saved in a non-volatile fashion.
For the components that have been replaced, the electronic rating plate must match as far as the following data is
concerned:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
For p9909 = 0, serial numbers and hardware versions are not automatically transferred. In this case, the transfer
must be made using p9904.
Dependency:
Refer to: p9904, p9905
Note:
The modified target topology is automatically saved in a non-volatile fashion when the drive object runs-up (e.g. after
a POWER ON).
Special case for Control Unit and option slot modules:
When replacing these components, independent of p9909, the serial number and hardware version are automatically
transferred and saved in a non-volatile fashion.
p9910

Target topology accept additional components / Add comp accept

CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: Topology
CU_G150_PN
Not for motor type: -
Min
0
Description:
Accept additional inserted DRIVE-CLiQ components into the target topology.
The corresponding drive objects are added to the project.
Value:
0:
1:
2:
3:
4:
5:
6:
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Minimum: Compares the component class
Topology has different comparison stages
No selection
Drive object type SERVO
Drive object type VECTOR
SINAMICS GM (DFEMV & VECTORMV)
SINAMICS SM (AFEMV & VECTORMV)
SINAMICS GL (VECTORGL)
SINAMICS SL (VECTORSL)
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
6
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
951

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents