p9399[0...1]
SI Motion reference checksum SI parameters (Motor Module) / SI Mtn setp CRC MM
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Sets the checksum for the checked Safety Integrated parameters of the motion monitoring function (reference
checksum) on the Motor Module/Hydraulic Module.
Index:
[0] = Checksum over SI parameters for motion monitoring
[1] = Checksum over SI parameters with hardware reference
Dependency:
Refer to: r9398
Note:
SI: Safety Integrated
r9406[0...19]
PS file parameter number parameter not transferred / PS par_no n transf
All objects
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the parameters that were not able to be transferred when reading the parameter back-up files (PS files)
from the non-volatile memory (e.g. memory card).
r9406[0] = 0
--> All of the parameter values were able to be transferred error-free.
r9406[0...x] > 0
--> indicates the parameter number in the following cases:
- parameter, whose value was not able to be completely accepted.
- indexed parameter, where at least 1 index was not able to be accepted. The first index that is not transferred is
displayed in r9407.
Dependency:
Refer to: r9407, r9408
Note:
All indices from r9406 to r9408 designate the same parameter.
r9406[x] parameter number, parameter not accepted
r9407[x] parameter index, parameter not accepted
r9408[x] fault code, parameter not accepted
r9407[0...19]
PS file parameter index parameter not transferred / PS parameter index
All objects
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the first index of the parameters that could not be transferred when the parameter backup files (PS files)
were read from the non-volatile memory (e.g. memory card).
If, from an indexed parameter, at least one index was not able to be transferred, then the parameter number is
displayed in r9406[n] and the first index that was not transferred is displayed in r9407[n].
r9406[0] = 0
--> All of the parameter values were able to be transferred error-free.
r9406[n] > 0
--> Displays r9407[n] the first index of the parameter number r9406[n] that was not transferred.
Dependency:
Refer to: r9406, r9408
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
FFFF FFFF hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-