Bi: Jog Bit 1 / Jog Bit 1; Jog 1 Speed Setpoint / Jog 1 N_Set; Jog 2 Speed Setpoint / Jog 2 N_Set; Speed Limit Setpoint Channel / N_Limit Setp - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
p1056[0...n]

BI: Jog bit 1 / Jog bit 1

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for jog 2.
Recommend.:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
p1058[0...n]

Jog 1 speed setpoint / Jog 1 n_set

VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
Refer to: p1055, p1056
p1059[0...n]

Jog 2 speed setpoint / Jog 2 n_set

VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency:
Refer to: p1055, p1056
p1063[0...n]

Speed limit setpoint channel / n_limit setp

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [rpm]
Description:
Sets the speed limit/velocity limit effective in the setpoint channel.
Dependency:
Refer to: p1082, p1083, p1085, p1086, p1088
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.000 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.000 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.000 [rpm]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2501, 3030
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3001, 3030
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 2
Func. diagram: 3001, 3030
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 1
Func. diagram: 3040
Unit selection: p0505
Expert list: 1
Factory setting
40000.000 [rpm]
295