Faults/Alarms Trigger Selection / F/A Trigger Sel; Co/Bo: Faults/Alarms Trigger Word / F/A Trigger Word - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
p2128[0...15]

Faults/alarms trigger selection / F/A trigger sel

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
See also: r2129
r2129.0...15

CO/BO: Faults/alarms trigger word / F/A trigger word

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the trigger signals of the faults/alarms set in p2128[0...15].
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
See also: p2128
Note
CO: r2129 = 0 --> None of the selected messages has occurred.
CO: r2129 > 0 --> At least one of the selected messages has occurred.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Signal name
Trigger signal p2128[0]
Trigger signal p2128[1]
Trigger signal p2128[2]
Trigger signal p2128[3]
Trigger signal p2128[4]
Trigger signal p2128[5]
Trigger signal p2128[6]
Trigger signal p2128[7]
Trigger signal p2128[8]
Trigger signal p2128[9]
Trigger signal p2128[10]
Trigger signal p2128[11]
Trigger signal p2128[12]
Trigger signal p2128[13]
Trigger signal p2128[14]
Trigger signal p2128[15]
Calculated: -
Scaling: -
Unit selection: -
Max:
65535
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Parameters
7.2 Parameter list
Data type: Unsigned16
Dynamic index: -
Function diagram: 8050, 8070
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: 8070
Factory setting:
-
0 signal
FP
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
OFF
-
773

Advertisement

Table of Contents
loading

Table of Contents