Torque Utilization Switch-Off Delay / M_Util T_Off; Torque Utilization Scaling / M_Util Scal; Co/Bo: Status Word Monitoring 1 / Zsw Monitor 1 - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p2195[0...n]

Torque utilization switch-off delay / M_util t_off

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: p2174, p2194
p2196[0...n]

Torque utilization scaling / M_util scal

VECTOR_G
Can be changed: C2(1, 3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.00 [%]
Description:
Sets the scaling factor for torque utilization (r0033).
r2197.1...13

CO/BO: Status word monitoring 1 / ZSW monitor 1

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and BICO output for the first status word of the monitoring functions.
Bit field:
Bit
01
02
03
06
07
13
Note:
Re bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
Re bit 03:
The hysteresis is set in p2150.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
Re bit 13:
Only for internal Siemens use.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
|n_act| <= speed threshold value 2 p2155
|n_act| > speed threshold value 2 p2155
n_act >= 0
|n_act| > n_max
Speed setp - act val deviation in tolerance
t_off
|n_act| > n_max (F07901)
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1000.0 [ms]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8012
Unit selection: -
Expert list: 1
Factory setting
800.0 [ms]
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 2534
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
FP
8010
8010
8011
8010
8011
-
525