Equivalent Zero Mark Input Terminal / Zm_Equiv Inp_Term; Equivalent Zero Mark Input Terminal / Zm_Equiv Input - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
Refer to the encoder interface for PROFIdrive.
The terminal must be set as input (p0728).
For p0493 = 0 (factory setting) the following applies:
- there is no logic operation between the reference mark search and an input signal.
For p0493 > 0, the following applies:
- the positive edge of the input signal is evaluated. If the negative edge is to be evaluated, signal inversion must be
parameterized via p0490.
- if a parameter change is rejected, a check should be performed as to whether the input terminal is already being
used in p0580, p0680, p2517, or p2518.
p0494[0...n]

Equivalent zero mark input terminal / ZM_equiv inp_term

VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Selects the input terminal for connecting an equivalent zero mark (external encoder zero mark).
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
Notice:
For CX32, NX10 and NX15, only DI/DO 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
For p0494 = 0 (factory setting), the setting in p0495 is effective.
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
Refer to the encoder interface for PROFIdrive.
The terminal must be set as input.
p0495

Equivalent zero mark input terminal / ZM_equiv input

ENC
Can be changed: U, T
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Selects the input terminal for connecting an equivalent zero mark (external encoder zero mark).
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
Notice:
For CX32, NX10 and NX15, only DI/DO 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
For p0494 > 0, the setting in p0494 is effective and p0495 is invalid.
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
200
No equivalent zero mark (evaluation of the encoder zero mark)
DI/DO 9 (X122.10/X121.8)
DI/DO 10 (X122.12/X121.10)
DI/DO 11 (X122.13/X121.11)
DI/DO 13 (X132.10/X131.2)
DI/DO 14 (X132.12/X131.4)
DI/DO 15 (X132.13/X131.5)
DI/DO 8 (X122.9/X121.7)
DI/DO 12 (X132.9/X131.1)
No equivalent zero mark (evaluation of the encoder zero mark)
DI/DO 9 (X122.10/X121.8)
DI/DO 10 (X122.12/X121.10)
DI/DO 11 (X122.13/X121.11)
DI/DO 13 (X132.10/X131.2)
DI/DO 14 (X132.12/X131.4)
DI/DO 15 (X132.13/X131.5)
DI/DO 8 (X122.9/X121.7)
DI/DO 12 (X132.9/X131.1)
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
8
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
8
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 4735
Unit selection: -
Expert list: 1
Factory setting
0