2 Parameters
2.2 List of parameters
r2198.4...12

CO/BO: Status word monitoring 2 / ZSW monitor 2

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and BICO output for the second status word of the monitoring functions.
Bit field:
Bit
04
05
06
07
10
11
12
Note:
Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
r2199.0...12

CO/BO: Status word monitoring 3 / ZSW monitor 3

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and BICO output for the third status word of the monitoring functions.
Bit field:
Bit
00
01
04
05
06
07
11
12
Note:
Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit is not reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
526
Signal name
|n_set| < p2161
n_set > 0
Motor blocked
Motor stalled
|M_set| < torque threshold value 1
Load monitoring signals an alarm
Load monitoring signals a fault condition
Signal name
|n_act| < speed threshold value 3
f or n comparison value reached or
exceeded
Speed setp - act val deviation in tolerance
t_on
Ramp-up/ramp-down completed
Current below the zero current threshold
Speed deviation model/external in tolerance Yes
Torque utilization < torque threshold value 2 Yes
Excitation current outside the tolerance
range
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 2536
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
Access level: 2
Func. diagram: 2537
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
SINAMICS G130/G150
FP
8011
8011
8012
8012
8012
8013
8013
FP
8010
8010
8011
8011
8018
8012
8012
8018

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents