Technology Controller Ramp-Up Time / Tec_Ctrl T_Ramp-Up; Technology Controller Ramp-Down Time / Tec_Ctrl T_Ramp-Dn; Co: Technology Controller Setpoint After Ramp-Function Generator; Technology Controller Setpoint Filter Time Constant - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p2257

Technology controller ramp-up time / Tec_ctrl t_ramp-up

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.00 [s]
Description:
Sets the ramp-up time of the technology controller.
Dependency:
Refer to: p2252, p2258
Note:
The ramp-up time is referred to 100 %.
p2258

Technology controller ramp-down time / Tec_ctrl t_ramp-dn

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.00 [s]
Description:
Sets the ramp-down time of the technology controller.
Dependency:
Refer to: p2252, p2257
Note:
The ramp-down time is referred to 100 %.
r2260
CO: Technology controller setpoint after ramp-function generator / Tec_ctr set aftRFG
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Sets the setpoint after the ramp-function generator of the technology controller.
p2261
Technology controller setpoint filter time constant / Tec_ctrl set T
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.000 [s]
Description:
Sets the time constant for the setpoint filter (PT1) of the technology controller.
r2262
CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Display and connector output for the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
650.00 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
650.00 [s]
Calculated: -
Dyn. index: -
Units group: 9_1
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
60.000 [s]
Calculated: -
Dyn. index: -
Units group: 9_1
Scaling: PERCENT
Max
- [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
1.00 [s]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
1.00 [s]
Access level: 2
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 3
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
537

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents