2 Parameters
2.2 List of parameters
p0778[0...2]

Test socket characteristic value y1 / Test skt char y1

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Terminals
CU_G150_PN
Not for motor type: -
Min
0.00 [V]
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the y coordinate (output voltage) of the first point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0779, p0780, r0786
p0779[0...2]

Test socket characteristic value x2 / Test skt char x2

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Terminals
CU_G150_PN
Not for motor type: -
Min
-100000.00 [%]
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the x coordinate (percentage) of the second point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0780, r0786
Note:
The value 100.00 % corresponds to 4.98 V.
p0780[0...2]

Test socket characteristic value y2 / Test skt char y2

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Terminals
CU_G150_PN
Not for motor type: -
Min
0.00 [V]
Description:
The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the y coordinate (output voltage) of the second point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0779, r0786
244
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4.98 [V]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
427.9E9 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4.98 [V]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
2.49 [V]
Access level: 2
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 8134
Unit selection: -
Expert list: 1
Factory setting
4.98 [V]
SINAMICS G130/G150