Motor Temperature Offset Pt100 / Mot T_Offset Pt100; Motor Ambient Temperature During Commissioning / Mot T_Ambient - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Dependency:
Refer to: p0621, r0623
Note:
For p0622 < p0346 the following applies:
If identification is activated, the magnetizing time is influenced by p0622. The speed is enabled after measurement is
complete, but not before the time in p0346 has elapsed (see r0056 bit 4). The time taken for measurement also
depends on the settling time of the measured current.
For p0622 >= p0346 the following applies:
Parameter p0622 is internally limited to the magnetizing time p0346, so that p0346 represents the maximum possible
magnetizing time during identification. The entire measurement period (magnetizing plus measurement settling time
plus measuring time) will always be greater than p0346.
r0623
Rs identification stator resistance after switch on again / Rs-id Rs aft sw-on
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor identification
Not for motor type: PEM, REL, FEM
Min
- [ohm]
Description:
Displays the stator resistance determined using the Rs identification after switching on again.
Dependency:
Refer to: p0621, p0622
p0624[0...n]

Motor temperature offset PT100 / Mot T_offset PT100

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-100.0 [K]
Description:
Sets the temperature offset for the PT100 measured value.
If there is a difference between the motor temperature displayed in r0035 and the actual motor temperature, this
offset can be entered in this parameter, thereby compensating for the difference.
Dependency:
Refer to: p0600, p0601, p0602
Note:
The parameter only takes effect with the following settings:
- Temperature sensor of the power unit detected (p0600 = 11).
- Sensor type PT100 selected (p0601 = 5).
If the resistance in series with the PT100 (e.g. the cable resistance of the feeder cable) is known, the following
conversion formula must be used:
Offset in p0624 = Measured resistance in ohms x 2.5 K/Ohm
Example:
Measured cable resistance = 2 Ohm
--> 2 Ohm x 2.5 K / Ohm = 5.0 K
p0625[0...n]

Motor ambient temperature during commissioning / Mot T_ambient

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-40 [°C]
Description:
Defines the ambient temperature of the motor for calculating the motor temperature model.
Dependency:
Refer to: p0350, p0354
Note:
The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
If the thermal I2t motor model is activated for permanent-magnet synchronous motors (refer to p0611), p0625 is
included in the model calculation if a temperature sensor is not being used (see p0601).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ohm]
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_2
Scaling: -
Max
100.0 [K]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: -
Max
80 [°C]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [ohm]
Access level: 3
Func. diagram: 8016
Unit selection: p0505
Expert list: 1
Factory setting
0.0 [K]
Access level: 3
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
20 [°C]
225