Si Safe Stop 1 Drive-Based Braking Response / Si Ss1 Drv Resp; Si Transition Time Stop F To Stop A (Control Unit) / Si Stop F->A Cu; Si Forced Checking Procedure Timer / Si Fcp Timer - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Recommend.:
In order that the drive can completely ramp-down along the OFF3 ramp and a motor holding brake that is possibly
available can close, then the delay time should be set as follows:
Motor holding brake parameterized: delay time >= p1135 + p1228 + p1217
Motor holding brake not parameterized: delay time >= p1135 + p1228
Dependency:
Refer to: p1135, p9852
Note:
For a crosswise data comparison between p9652 and p9852, a difference of one Safety monitoring clock cycle is
tolerated.
The set time is rounded internally to an integer multiple of the monitoring clock (r9780/r9880) cycle.
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
p9653

SI Safe Stop 1 drive-based braking response / SI SS1 drv resp

VECTOR_G
Can be changed: C2(95)
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the drive-based braking response for the "Safe Stop 1" (SS1) function.
Value:
0:
1:
Note:
SS1: Safe Stop 1 (Safe Stop 1, corresponds to Stop Category 1 acc. to EN60204)
SS1E: Safe Stop 1 external (Safe Stop 1 with external stop)
SS1E requires the externally initiated stop in order to be in conformance with stop Category 1.
With this parameter, a switchover is made from SS1 to SS1E, and the drive-based braking response of function SS1
(time controlled) of the Basic Functions is deactivated.
p9658
SI transition time STOP F to STOP A (Control Unit) / SI STOP F->A CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition period from STOP F to STOP A on the Control Unit.
Dependency:
Refer to: r9795, p9858
Note:
For a crosswise data comparison between p9658 and p9858, a difference of one Safety monitoring clock cycle is
tolerated.
The set time is rounded internally to an integer multiple of the monitoring clock (r9780/r9880) cycle.
STOP F: Defect in a monitoring channel (error in the crosswise data comparison)
STOP A: STO as a result of a fault detected by Safety Integrated
p9659

SI forced checking procedure timer / SI FCP Timer

VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [h]
Description:
Sets the time interval for carrying out the forced checking procedure and testing the Safety shutdown paths.
Within the parameterized time, STO must have been de-selected at least once. The monitoring time is reset each
time that STO is de-selected.
Note:
STO: Safe Torque Off / SH: Safe standstill
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
SS1 with OFF3
SS1E external stop
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
30000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
9000.00 [h]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2802
Unit selection: -
Expert list: 1
Factory setting
0.00 [ms]
Access level: 3
Func. diagram: 2810
Unit selection: -
Expert list: 1
Factory setting
8.00 [h]
907