2 Parameters
2.2 List of parameters
p1545[0...n]

BI: Activates travel to a fixed stop / TfS activation

VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: REL
Min
-
Description:
Sets the signal source to activate/de-activate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
EPOS uses the parameter (refer to p2686).
When traveling to fixed stop, the fault F07900 "motor blocked" is suppressed.
r1547[0...1]

CO: Torque limit for speed controller output / M_max outp n_ctrl

VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Nm]
Description:
Displays the torque limit to limit the speed controller output.
Index:
[0] = Upper limit
[1] = Lower limit
r1548[0...1]

CO: Stall current limit torque-generating maximum / Isq_max stall

VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Arms]
Description:
Displays the limit for the torque-generating current component using the stall calculation, the current limit of the Motor
Module as well as the parameterization in p0640.
Index:
[0] = Upper limit
[1] = Lower limit
p1551[0...n]

BI: Torque limit variable/fixed signal source / M_lim var/fixS_src

VECTOR_G (n/M)
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source to change over the torque limits between variable and fixed torque limit.
BI: p1551 = 1 signal:
The variable torque limit applies (fixed torque limit + scaling).
BI: p1551 = 0 signal:
The fixed torque limit applies.
386
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: 7_1
Scaling: p2003
Max
- [Nm]
Calculated: -
Dyn. index: -
Units group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2520, 3617,
8012
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 6060
Unit selection: p0505
Expert list: 1
Factory setting
- [Nm]
Access level: 4
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: 5620, 5630,
6060, 6630
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150