Acknowledge Si Motion Data Change / Ackn Si Mtn Dat; Si Acknowledge Component Replacement / Comp_Replace Ackn - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

87:
208:
Note:
Re value = 57 hex, 2E hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
Re value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9602 --> p9802, p9610 --> 9810, p9611 --> 9811, p9621 --> 9821, p9622 --> 9822, p9650 -->
p9850, p9651 --> p9851, p9652 --> p9852, p9658 --> p9858, p9697 --> p9897
p9701

Acknowledge SI motion data change / Ackn SI Mtn dat

TM54F_MA,
Can be changed: C2(95), U, T
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
Value:
0:
172:
236:
Dependency:
Refer to: r9398, p9399, r9728, p9729, r9798, p9799, r9898, p9899
Note:
Re value = AC hex:
These values can only be set if the safety commissioning mode is set and the Safety Integrated password was
entered.
SI: Safety Integrated
p9701
Acknowledge SI motion data change / Ackn SI Mtn dat
VECTOR_G
Can be changed: C2(95), U, T
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
Value:
0:
172:
220:
236:
Dependency:
Refer to: r9398, p9399, r9728, p9729, r9798, p9799, r9898, p9899
Note:
Re value = AC and DC hex:
These values can only be set if the safety commissioning mode is set and the Safety Integrated password was
entered.
p9702

SI Acknowledge component replacement / Comp_replace ackn

VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Setting to acknowledge that a component has been replaced.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
[57 hex] Start copy function SI parameters
[D0 hex] Start copy function SI basic parameters
[00 hex] Data unchanged
[AC hex] Acknowledge data change complete
[EC hex] Acknowledge hardware CRC
[00 hex] Data unchanged
[AC hex] Acknowledge data change complete
[DC hex] Acknowledge SI basic parameter change
[EC hex] Acknowledge hardware CRC
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
00EC hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
00EC hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
29
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
911