2 Parameters
2.2 List of parameters
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293

Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294

CO: Technology controller output signal / Tec_ctrl outp_sig

VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Display and connector output for the output signal of the technology controller.
Dependency:
Refer to: p2295
p2295

CO: Technology controller output scaling / Tec_ctrl outp scal

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-100.00 [%]
Description:
Sets the scaling for the output signal of the technology controller.
p2296[0...n]

CI: Technology controller output scaling / Tec_ctrl outp scal

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the scaling value of the technology controller.
Dependency:
Refer to: p2295
p2297[0...n]
CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the maximum limiting of the technology controller.
Dependency:
Refer to: p2291
542
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100.00 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
100.00 [%]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
1.00 [s]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
2295[0]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
2291[0]