Par_Circuit Power Unit Number, Temperature Sensor / Pu_No Temp_Sensor; Ci: Motor Temperature Signal Source / Mot Temp S_Src - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
A thermal motor model is calculated corresponding to p0612.
Refer to: r0458, p0600, p0612
Note:
The temperature sensor for the temperature evaluation is set in p0600.
For p0600 = 10 (temperature sensor via a BICO interconnection), the setting in p0601 has no significance.
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Re p0601 = 1:
Tripping resistance = 1650 Ohm.
After the tripping resistance has been exceeded, an appropriate alarm is output and after the delay time set in p0606
has expired, an appropriate fault is output.
Re p0601 = 3:
For motors with DRIVE-CLiQ and 2 temperature sensors, the value is automatically set.
Re p0601 = 4:
Tripping resistance = 100 Ohm.
After tripping, an appropriate alarm is output and after the delay time set in p0606 has expired, an appropriate fault is
output.
Re p0601 = 5:
It is only possible to evaluate a PT100 for p0600 = 11 and r0192.15 = 1.
Re p0601 = 10:
Not permitted for p0600 = 0, 10, 11.
Associated parameters: p4600 ... p4603 (can be switched via EDS)
For r0458.8 = 1, a temperature evaluation is supported through several temperature channels.
Examples:
When evaluating using SME120 or SME125, 4 temperature channels are available ( parameterized using p4600,
p4601, p4602, p4603).
When evaluating using CU310 and CUA32, 2 temperature channels are available (encoder interface:
parameterization via p4600, terminal block: parameterization via p4601).
Re p0601 = 11:
Not permitted for p0600 = 0, 10, 11.
Associated parameters: p4610 ... p4613 (can be switched via MDS)
p0602

Par_circuit power unit number, temperature sensor / PU_no temp_sensor

VECTOR_G (Parallel) Can be changed: C2(3), U, T
Data type: Unsigned16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the power unit number to which the temperature sensor is connected. The value corresponds to the Power unit
Data Set number (PDS) of the power unit. The number of power unit data sets is defined in p0120.
p0603

CI: Motor temperature signal source / Mot temp S_src

VECTOR_G
Can be changed: C2(3), T
Data type: Unsigned32 / FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets the signal source to evaluate the motor temperature via a BICO interconnection.
Dependency:
Refer to: p0600
Note:
Temperature sensor KTY: Valid temperature range -48 °C ... 248 °C.
PTC temperature sensor:
For a value = -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC.
For a value = 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC.
218
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
10
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2006
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150