r5398[0...n]

Mot_temp_mod 3 alarm threshold image p5390 / A thr image p5390

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: ASM, REL, FEM
Min
- [°C]
Description:
Displays the alarm threshold for monitoring the motor temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p5390.
Note:
Users cannot see and change parameter p5390 (only Siemens internal).
r5399[0...n]

Mot_temp_mod 3 fault threshold image p5391 / F thr image p5391

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: ASM, REL, FEM
Min
- [°C]
Description:
Sets the fault threshold for monitoring the motor temperature for motor temperature model 3.
Fault F07011 is output after the fault threshold is exceeded.
The parameter value is an image of p5391.
Note:
Users cannot see and change parameter p5391 (only Siemens internal).
r5600

Pe energy saving mode ID / Pe mode ID

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
0
Description:
Displays the PROFIenergy mode ID of the effective energy saving mode.
Value:
0:
2:
255:
Note:
Pe: PROFIenergy profiles
p5602[0...1]

Pe energy-saving mode pause time minimal / Pe mod t_pause min

CU_G130_DP,
Can be changed: T
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
300000 [ms]
Description:
Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, dwell time minimal
Index:
[0] = Reserved
[1] = Mode 2
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
POWER OFF
Energy-saving mode 2
Ready
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: -
Max
- [°C]
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: -
Max
- [°C]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295 [ms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
Access level: 2
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2381
Unit selection: -
Expert list: 1
Factory setting
[0] 300000 [ms]
[1] 480000 [ms]
693