p3202[0...n]
Excitation current outside the tolerance hysteresis / I_exc n Tol hyst
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.1 [%]
Description:
Sets the hysteresis for the "excitation current outside tolerance" message for the excitation current monitoring.
Dependency:
Refer to: p3201, p3203
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
p3203[0...n]
Excitation current outside the tolerance delay time / I_exc n Tol t_del
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.0 [s]
Description:
Sets the delay time for the "excitation current outside tolerance" message for the excitation current monitoring.
Dependency:
Refer to: p3201, p3202
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
p3204[0...n]

Flux outside the tolerance threshold value / Flux n tol thresh

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.1 [%]
Description:
Sets the threshold value for the "flux outside the tolerance" message for the flux monitoring.
If the absolute value of the difference between the flux setpoint and actual value (r0083 - r0084) falls below the
threshold value with hysteresis longer than the selected delay time, then fault F07914 is output.
This fault is withdrawn when the threshold voltage is undershot.
Dependency:
Refer to: r0083, r0084, p3205, p3206
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
p3205[0...n]

Flux outside the tolerance hysteresis / Flux n tol hyst

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.1 [%]
Description:
Sets the hysteresis for the "flux outside tolerance" message for the flux monitoring.
Dependency:
Refer to: p3204, p3206
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.0 [s]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
50.0 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.0 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.0 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.0 [%]