Component Trace Trigger / Comp Trace Trigger - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

For p7790[0...15] = 0, the component trace is deactivated.
Re index 0 ... 7:
The signals are set in p7790[0...7], whose characteristic is to be recorded over time.
If "No signal" is set for a trace channel, then the recording duration of the other time characteristics is increased.
Re index 8 ... 15:
The signals are set in p7790[8...15], whose instantaneous value is to be recorded.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
Index:
[0] = Trace channel 0
[1] = Trace channel 1
[2] = Trace channel 2
[3] = Trace channel 3
[4] = Trace channel 4
[5] = Trace channel 5
[6] = Trace channel 6
[7] = Trace channel 7
[8] = Trace channel 8
[9] = Trace channel 9
[10] = Trace channel 10
[11] = Trace channel 11
[12] = Trace channel 12
[13] = Trace channel 13
[14] = Trace channel 14
[15] = Trace channel 15
Dependency:
Refer to: p7791, p7792
Note:
In the operation state, when a trigger event occurs, the trace data of the signals are saved in the component. The
oldest trace data are overwritten after more than 5 trigger events.
The trigger event can be set in p7791.
By activating p7792, the trace data of the component is written to files on the non-volatile storage medium (memory
card). Experts can then evaluate this data.
p7791

Component trace trigger / Comp trace trigger

B_INF, VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the trigger event for the component trace.
Value:
0:
1:
2:
Dependency:
Refer to: p7790, p7792
Note:
When the power unit detects an overcurrent condition, then A30001 is output.
When the power unit detects an overvoltage condition in the DC link, then A30002 is output.
When the power unit detects a ground fault, then A30021 is output.
When the power unit detects a Uce fault, then A30022 is output.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
No signal
Pulse frequency
Phase current U
Phase current V
Phase current W
IGBT chip temperature
Heat sink temperature
DC link voltage
Modulat_depth
Angle
Overcurrent, overvoltage, ground fault, Uce
Time-critical message
Uce
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
725