Macro Binector Input (Bi) For Tms / Macro Bi Tm; Cu Digital Inputs Terminal Actual Value / Cu Di Term Act Val - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
The binector inputs of the corresponding command data set are appropriately interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency:
Refer to: p0015, p1000, p1500, r8571
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
p0700

Macro Binector Input (BI) for TMs / Macro BI TM

TB30, TM31
Can be changed: C2(1), T
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
0
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency:
Refer to: r8571
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
r0721

CU digital inputs terminal actual value / CU DI term act val

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
CU_G150_PN
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p0795.x = 1) to terminal mode (p0795.x = 0).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
236
Signal name
DI 0 (X122.1/X121.1)
DI 1 (X122.2/X121.2)
DI 2 (X122.3/X121.3)
DI 3 (X122.4/X121.4)
DI 4 (X132.1 / -)
DI 5 (X132.2 / -)
DI 6 (X132.3 / -)
DI 7 (X132.4 / -)
DI/DO 8 (X122.9/X121.7)
DI/DO 9 (X122.10/X121.8)
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
999999
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
High
High
High
High
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2020, 2030,
2031, 2100, 2119, 2120, 2130,
2131, 2132, 2133
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130