Comm If Error Statistics / Comm Err; Field Bus Interface Baud Rate / Field Bus Baud; Field Bus Interface Address / Field Bus Address - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r2019[0...7]

Comm IF error statistics / Comm err

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the receive errors at the commissioning interface (RS232).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2020

Field bus interface baud rate / Field bus baud

CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
4
Description:
Sets the baud rate for the fieldbus interface USS.
Value:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
Note:
Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
p2021

Field bus interface address / Field bus address

CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Displays or sets the address for the fieldbus interface USS.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p2021 displays the address setting.
--> A change only becomes effective after a POWER ON.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
2400 baud
4800 baud
9600 baud
19200 baud
38400 baud
57600 baud
76800 baud
93750 baud
115200 baud
187500 baud
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
13
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
31
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
8
Access level: 2
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
0
463