2 Parameters
2.2 List of parameters
p1152

BI: Setpoint 2 enable / Setp 2 enab

VECTOR_G (Ext
Can be changed: T
brake)
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for "setpoint 2 enable".
p1155[0...n]

CI: Speed controller speed setpoint 1 / n_ctrl n_set 1

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for speed setpoint 1 of the speed controller.
Dependency:
The effectiveness of this setpoint depends on, e.g. STW1.4 and STW1.6.
Refer to: r0002, p0840, p0844, p0848, p0852, p0854, r0898, p1140, p1142, p1160, r1170, p1189
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1160[0...n]

CI: Speed controller speed setpoint 2 / n_ctrl n_set 2

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for speed setpoint 2 of the speed controller.
Dependency:
Refer to: p1155, r1170
Note:
For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (SERVO: to the actual value, VECTOR: To the setpoint (r1170)) and stops the
drive corresponding to the ramp-downtime (p1121 or p1135). While stopping via the ramp-function generator,
STW1.4 is effective (enable ramp-function generator).
When the function module "position control" (r0108.3 = 1) is activated, this connector input is interconnected as
follows as standard:
CI: p1160 = r2562
r1169

CO: Speed controller speed setpoints 1 and 2 / n_ctrl n_set 1/2

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the speed setpoint after the addition of the speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency:
Refer to: p1155, p1160
Note:
The value is only correctly displayed at r0899.2 = 1 (operation enabled).
310
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2000
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2000
Max
-
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2711, 4015
Unit selection: -
Expert list: 1
Factory setting
899.15
Access level: 3
Func. diagram: 3001, 3080,
5030, 6031
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3001, 3080
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3080
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]