Warning:
Check that binector outputs BO: r3861.n are connected correctly and that the appropriate digital outputs are wired
correctly.
If the interconnection/wiring is incorrect, the software could execute a different (incorrect) function via binector
outputs BO: r3861.n if the Braking Module develops a fault.
p3862

Braking Module DC link fast discharge delay time / BM DC-dischg t_del

B_INF (Brk Mod ext)
Can be changed: C1(3), T
Data type: Unsigned32
P-Group: Communications
Not for motor type: -
Min
500 [ms]
Description:
Sets the delay time for switching in the DC link fast discharge.
Dependency:
Refer to: p3863, r3864
Note:
The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis"
formats.
p3863
BI: Activating Braking Module DC link fast discharge / BM DC-dischg act
B_INF (Brk Mod ext)
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source to activate the DC link fast discharge.
The DC link fast discharge is started later with delay time (p3862) when the following conditions apply:
- BI: p3863 = 1 signal.
- an external line contactor is opened via r0863.1 "energize contactor".
The DC link fast discharge is interrupted when the following conditions apply:
- BI: p3863 = 0 signal.
- ON command for the infeed.
Recommend.:
The DC link fast discharge should be activated if there is an external line contactor and is correctly interconnected
(r0863.1, p0860). If the DC link fast discharge is not activated together with an external line contactor, then faults
could occur when pre-charging (e.g. F30027).
Dependency:
Refer to: r3864
Note:
The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis"
formats.
r3864.0...7

BO: Braking Module DC link fast discharge / BM DC link dischg

B_INF (Brk Mod ext)
Can be changed: -
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
-
Description:
Signal to control (energize) terminal X21.2 "DC link fast discharge" on the Braking Module.
This binector output is used as signal source to interconnect to a digital output. The digital output must be connected
to terminal X21.2 of the particular Braking Module.
Bit field:
Bit
00
01
02
03
04
05
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Fast discharge Braking Module 1
Fast discharge Braking Module 2
Fast discharge Braking Module 3
Fast discharge Braking Module 4
Fast discharge Braking Module 5
Fast discharge Braking Module 6
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
1000 [ms]
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
FP
-
-
-
-
-
-
589