2 Parameters
2.2 List of parameters
r3662[0...n]

CO: VSM input line supply voltage u2 - u3 / VSM inp u2-u3

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [V]
Description:
Displays the input voltage between phases L2 and L3 for the Voltage Sensing Module (VSM).
Dependency:
Refer to: p3660
Note:
X521.1 or X522.1: Connection of L1
X521.2 or X522.2: Connection of L2
X521.3 or X522.3: Connection of L3
r3664[0...n]

CO: VSM temperature evaluation status / VSM temp status

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Displays the status of the temperature evaluation of the Voltage Sensing Module (VSM).
This displays whether the temperature actual value has exceeded the fault/alarm threshold.
Bit field:
Bit
00
01
Dependency:
Refer to: p3665, r3666, p3667, p3668
p3665[0...n]

VSM temperature evaluation sensor type / VSM TempSensorType

VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Closed-loop control
Not for motor type: -
Min
0
Description:
Setting of the temperature sensor for the Voltage Sensing Module (VSM).
The temperature sensor is connected to terminals X520.5 and X520.6 of the VSM.
Value:
0:
1:
2:
Note:
The pre-assignment of the parameter depends on the device type.
For chassis power units, the temperature monitoring of the line filter is active (p3665 = 2).
r3666[0...n]

CO: VSM temperature KTY / VSM temp KTY

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [°C]
Description:
Displays the temperature actual value of a KTY84 temperature sensor connected to the Voltage Sensing Module
(VSM).
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
572
Signal name
Alarm is present
Fault is present
No sensor
PTC
KTY84
Calculated: -
Dyn. index: p0150
Units group: 5_3
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: p0150
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Calculated: -
Dyn. index: p0150
Units group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: p0150
Units group: 21_1
Scaling: p2006
Max
- [°C]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: 9886
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
Access level: 3
Func. diagram: 9886
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9886
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]