Profibus Diagnostics Standard / Pb Diag Standard; Profibus Address Switch Diagnostics / Pb Addr_Sw Diag; Co: If1 Profidrive Pzd Receive Double Word / If1 Pzd Recv Dw - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r2055[0...2]

PROFIBUS diagnostics standard / PB diag standard

CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Diagnostics display for the PROFIBUS interface.
Index:
[0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
r2057

PROFIBUS address switch diagnostics / PB addr_sw diag

CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency:
Refer to: p0918
Notice:
The display is updated after switching on, and not cyclically.
r2060[0...2]

CO: IF1 PROFIdrive PZD receive double word / IF1 PZD recv DW

ENC
Can be changed: -
Data type: Integer32
P-Group: Communications
Not for motor type: -
Min
-
Description:
Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
Dependency:
Refer to: r2050
Notice:
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Note:
IF1: Interface 1
r2060[0...30]
CO: IF1 PROFIdrive PZD receive double word / IF1 PZD recv DW
VECTOR_G
Can be changed: -
Data type: Integer32
P-Group: Communications
Not for motor type: -
Min
-
Description:
Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
478
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: 4000H
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: 4000H
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2440, 2468
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2440, 2468
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents