Co/Bo: Command Data Set Cds Selected / Cds Selected; Co/Bo: Drive Data Set Dds Selected / Dds Selected - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
This parameter is only supplied with up-to-date values if data set changeover has been selected or is running.
Re bit 00:
The signal is only influenced when a motor changeover is set via p0827 (unequal bit numbers).
Re bit 01:
The signal is only influenced when an encoder changeover is set via p0187, p0188, or p0189.
Re bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
Re bit 04:
A data set changeover is only carried out when the armature short circuit is not activated.
Re bit 05:
The following applies for SERVO:
A data set changeover is only carried out when pole position identification, encoder adjustment, motor data
identification, and rotating measurement are not running.
The following applies for VECTOR:
A data set changeover is only carried out when pole position identification is not running.
Re bit 06:
A data set changeover is only carried out when the friction characteristic record is not running.
Re bit 07 (VECTOR only):
A data set changeover is only carried out when rotating measurement is not running.
Re bit 08 (VECTOR only):
A data set changeover is only carried out when motor data identification is not running.
Re bit 10:
A motor changeover is set with p0833.1 = 1. It can only be carried out when the application performs pulse
suppression.
Re bit 11:
A motor changeover is set with p0833.0 = 1. The pulses are only enabled when the "Motor changeover feedback"
signal is detected.
r0836.0...3

CO/BO: Command Data Set CDS selected / CDS selected

B_INF, VECTOR_G
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the command data set (CDS) selected via the binector input.
Bit field:
Bit
00
01
02
03
Dependency:
Refer to: r0050, p0810, p0811
Note:
Command data sets are selected via binector input p0810 and following.
The currently effective command data set is displayed in r0050.
r0837.0...4

CO/BO: Drive Data Set DDS selected / DDS selected

ENC, VECTOR_G
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the drive data set (DDS) selected via the binector input.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
CDS select. bit 0
CDS select. bit 1
CDS select. bit 2
CDS select. bit 3
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
ON
ON
ON
ON
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8560
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
OFF
OFF
OFF
OFF
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
-
FP
-
-
-
-
255