Mitsubishi Electric Q173CPU Programming Manual page 365

Q series motion controller
Hide thumbs Also See for Q173CPU:
Table of Contents

Advertisement

11 MOTION SFC PARAMETER
Error code
(Note)
Event task
consecutive
17001
transition count
error
NMI task
consecutive
17002
transition
count error
POINT
Since the execute task can be set for every Motion SFC program No., multiple
programs need not be written for single control (machine operation) to divide
execution timing-based processing's.
For example, it can be achieved easily by subroutine starting the areas to be run
in fixed cycle and to be run by external interrupt partially in the Motion SFC
program run by the normal task.
(3) Number of consecutive transitions
[Description]
Set the number of consecutive transitions to program executed by the event or
NMI task for every program.
Refer to Section "11.4 Task Parameters" for number of consecutive transitions.
[Errors]
This program parameter is imported when the PLC ready flag (M2000) turns off
to on, and is checked at starting of the Motion SFC program (automatic start,
start from PLC or subroutine start).
When the value is illegal, either of the following Motion SFC errors is set and
the initial value is controlled.
Error cause
Name
Contents
The number of
consecutive
transitions of the
Motion SFC program
started by the event
task is outside the
range 1 to 10.
The number of
consecutive
transitions of the
Motion SFC program
started by the NMI
task is outside the
range 1 to 10.
Error processing
The initial value
of 1 is controlled.
11 - 14
Corrective action
Turn PLC ready flag (M2000) off,
make correction to set the value
of within the range, and write it to
the CPU.
(Note) : 0000H (normal)