5.5.6 Motor parameters

Check the safety conditions surrounding the motor and load machineries
before autotuning as physical injury may occur due to sudden start of motor
during autotuning.
Although the motor does not run during static autotuning, the motor is still
supplied with power. Do not touch the motor during autotuning; otherwise,
electric shock may occur. Do not touch the motor before autotuning is
completed.
If the motor has been connected to a load, do not carry out rotary autotuning.
Otherwise, the VFD may malfunction or may be damaged. If rotary
autotuning is carried out on a motor which has been connected to a load,
incorrect motor parameter settings and motor action exceptions may occur.
Disconnect from the load to carry out autotuning if necessary.
The VFD can drive both asynchronous motors and synchronous motors, and it supports two
sets of motor parameters, which can be switched over by multifunction digital input terminals
or communication modes.
Terminal
(P00.01=1)
P08.31 set LED
ones to 0
Terminal function 35
Motor 1 switches to
motor 2
Invalid
Name
-250.0–250.0%
-300.0–300.0% (of the motor rated current)
value
Start
Select running
command channel
(P00.01)
Keypad (P00.01=0)
The switch-over
channel for motor 1 and
motor 2 (P08.31)
P08.31 set LED
ones to 1
Valid
Motor 1
Description
Communication
(P00.01=2)
P08.31 sets
ones to 2
PROFIBUS/
MODBUS
CANopen/DeviceNet
communication
communication
Communication setting value
2009H
BIT0–1=01
BIT0–1=00
Motor 2
-73-
Basic operation guidelines
P08.31 sets
P08.31 sets
ones to 4
ones to 3
Ethernet
communication
Default
0.0%
0.0%
EtherCAT/Profinet
communication