Kruger Ecowatt K320 Series Operation Manual page 77

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
code
Reactive current
closed-loop
P04.38
integral time in
SM V/F control
Reactive current
closed-loop
P04.39
output limit in
SM V/F control
Enabling IF mode
P04.40
Current setting in
P04.41
IF mode for AM 1
Proportional
coefficient in IF
P04.42
mode for AM 1
proportional
coefficient
P04.43
coefficient in IF
mode for AM 1
Frequency
threshold for
P04.44
switching off IF
mode for AM 1
Enabling IF mode
P04.45
Name
When the SM V/F control mode is enabled,
the function code is used to set the integral
coefficient of reactive current closed-loop
control.
Setting range: 0–3000
When the SM V/F control mode is enabled,
the function code is used to set the output
limit of the reactive current closed-loop
control. A greater value indicates a higher
reactive closed-loop compensation voltage
and higher output power of the motor. In
general, you do not need to modify the
function code.
Setting range: 0–16000
0: Disable
of AM 1
1: Enable
When IF control is adopted for AM 1, the
function code is used to set the output current.
The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0–200.0%
When IF control is adopted for AM 1, the
function code is used to set the proportional
coefficient of the output current closed-loop
control.
Setting range: 0–5000
When IF control is adopted for AM 1, the
Integral
function code is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0–5000
0.00–P04.50
0: Disable
for AM 2
1: Enable
Description
-68-
Basic operation guidelines
Default
30
8000
0
120.0%
650
350
10.00Hz
0