Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
code
Setting source of
reverse rotation
upper-limit
P03.15
frequency in
torque control
Forward rotation
upper-limit
P03.16
frequency set
through keypad
in torque control
Reverse rotation
upper-limit
frequency set
P03.17
through keypad
in torque control
Setting source of
electromotive
P03.18
torque upper limit
Setting source of
braking torque
P03.19
upper limit
Electromotive
torque upper limit
P03.20
set through
keypad
Braking torque
P03.21
upper limit set
through keypad
Name
0: Keypad (P03.17)
1–11: Same as those of P03.14
0.00Hz–P00.03 (Max. output frequency)
0.00Hz–P00.03 (Max. output frequency)
0: Keypad (P03.20)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Modbus communication
6: PROFIBUS/CANopen/DeviceNet
communication
7: Ethernet communication
8: Pulse frequency HDIB
9: EtherCAT/PROFINET communication
10: PLC
11: Reserved
Note: For setting sources 1–4 and 8, 100%
corresponds to three times the rated motor
current.
0: Keypad (P03.21)
1–10: Same as those for P03.18
0.0–300.0% (of the motor rated current)
0.0–300.0% (of the motor rated current)
Description
-72-
Basic operation guidelines
Default
50.00 Hz
50.00 Hz
180.0%
180.0%
0
0
0