Kruger Ecowatt K320 Series Operation Manual page 80

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
code
Speed control
P00.00
Enabling torque
P03.32
control
Torque setting
P03.11
method
Torque set
P03.12
through keypad
Torque reference
P03.13
filter time
Setting source of
forward rotation
upper-limit
P03.14
frequency in
torque control
Name
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
mode
Note: To select 0, 1, or 3 as the control mode,
enable the VFD to perform motor parameter
autotuning first.
0: Disable
1: Enable
1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDIA
6: Multi-step torque
7: Modbus communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFINET communication
12: PLC
Note: For setting sources 2–6 and 10, 100%
corresponds to three times the rated motor
current.
-300.0%–300.0% (of the motor rated current)
0.000–10.000s
0: Keypad (P03.16)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi-step setting
6: Modbus/Modbus TCP communication
7: Profibus/CANopen/DeviceNet communication
8: Ethernet communication
9: Pulse frequency HDIB
10: EtherCat/Profinet/EtherNetIP communication
11: Programmable expansion card
12: Reserved
Note: For setting methods 1–11, 100% corresponds
to the maximum frequency.
Description
-71-
Basic operation guidelines
Default
50.0%
0.010s
2
0
0
0