Kruger Ecowatt K320 Series Operation Manual page 201

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Differential time
P09.06
(Td)
P09.07 Sampling cycle (T)
Limit of PID
P09.08
control deviation
Upper limit value
P09.09
of PID output
Lower limit value
P09.10
of PID output
Description
It
determines
the
regulation made on the change rate of
deviation between PID feedback and
reference by PID regulator. If feedback
changes by 100% during this period, the
regulation
of
(ignoring integral and differential actions)
is max. output frequency (P00.03) or max.
voltage (P04.31).
The longer the derivative time, the
stronger the regulation intensity. Setting
range: 0.00–10.00s
It means the sampling cycle of feedback.
The regulator operates once during each
sampling cycle. The larger the sampling
cycle, the slower the response.
Setting range: 0.001–10.000s
It is the max. allowable deviation of PID
system output value relative to closed-loop
reference value. Within this limit, PID
regulator
stops
function code properly to regulate the
precision and stability of PID system.
Reference
Output
frequency f
Setting range: 0.0–100.0%
The two function codes are used to set the
upper/lower limit value of PID regulator.
100.0%
corresponds
frequency
(P00.03)
(P04.31).
Setting range of P09.09: P09.10–100.0%
Setting range of P09.10: -100.0%–P09.09
-192-
intensity
of
differential
regulator
regulation.
Set
Deviation
Feedback
limit
Time t
Time t
to
Max.
output
or
max.
voltage
Function parameter list
Default Modify
the
0.00s
0.001s
this
0.0%
100.0%
0.0%