Function
Name
code
High-frequency
current-loop
P03.37
proportional
coefficient
High-frequency
P03.38
current-loop
integral coefficient
Current-loop
high-frequency
P03.39
switching
threshold
Enabling inertia
P03.40
compensation
Upper limit of
inertia
P03.41
compensation
torque
Inertia
P03.42
compensation
filter times
Inertia
P03.43
identification
torque value
Enabling inertia
P03.44
identification
P03.45–
Reserved
P03.46
Description
In the closed-loop vector control mode
(P00.00=3), when the frequency is lower
than
the
current-loop
switching
threshold
current-loop PI parameters are P03.09 and
P03.10; and when the frequency is higher
than
the
current-loop
switching
threshold
current-loop PI parameters are P03.37 and
P03.38.
Setting range of P03.37: 0–20000
Setting range of P03.38: 0–20000
Setting range of P03.39: 0.0–100.0% (of the
maximum frequency)
0: Disable
1: Enable
The max. inertia compensation torque is
limited to prevent inertia compensation
torque from being too large.
Setting range: 0.0–150.0% (of the motor
rated torque)
Filter
times
of inertia
torque,
used
compensation torque.
Setting range: 0–10
Due to friction force, it is required to set
certain identification torque for the inertia
identification to be performed properly.
Setting range: 0.0–100.0% (of the motor
rated torque)
0: No operation
1: Enable
-153-
high-frequency
(P03.39),
high-frequency
(P03.39),
compensation
to
smooth
inertia
Function parameter list
Default Modify
1000
the
1000
the
100.0%
0
10.0%
7
10.0%
0