Kruger Ecowatt K320 Series Operation Manual page 219

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Communication
P14.04
timeout time
Transmission
P14.05
error processing
Communication
P14.06
processing action
User-defined
running command
P14.07
address
User-defined
frequency setting
P14.08
address
Modbus-TCP
communication
P14.09
timeout time
Description
0.0 (invalid)–60.0s
When the function code is set to 0.0, the
communication timeout time is invalid.
When the function code is set a non-zero
value, the rectifier reports the "
Modbus/Modbus TCP communication
fault" (CE) if the communication interval
exceeds the value.
In general, the function code is set to 0.0.
When
continuous
required, you can set the function code to
monitor communication status.
0: Report an alarm and coast to stop
1: Keep running without reporting an
alarm
2: Stop in enabled stop mode without
reporting an alarm (applicable only to
communication mode)
3: Stop in enabled stop mode without
reporting an alarm (applicable to any
mode)
0x00–0x11
Ones place:
0: Respond to write operations
1: Not respond to write operations
Tens place:
0: Password protection for communication
is invalid.
1: Password protection for communication
is valid.
0x0000–0xFFFF
User-defined Modbus running command
address
0x0000–0xFFFF
User-defined Modbus frequency setting
address
0.0 (invalid)–60.0s
-210-
Function parameter list
communication
is
Default Modify
0.0s
0
0x00
0x2000
0x2001
0.0s