Kruger Ecowatt K320 Series Operation Manual page 179

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
P06 group––Output terminals
Function
Name
code
P06.00
HDO output type
P06.01
Y1 output
P06.02
HDO output
P06.03
RO1 output
P06.04
RO2 output
Description
0: Open collector high-speed pulse output.
The max. frequency of pulse is 50.00kHz.
For details about the related functions, see
P06.27–P06.31.
1: Open collector output. For details about
the related functions, see P06.02.
0: Invalid
1: Running
2: Running forward
3: Running reversely
4: Jogging
5: VFD in fault
6: Frequency level detection FDT1
7: Frequency level detection FDT2
8: Frequency reached
9: Running in zero speed
10: Upper limit frequency reached
11: Lower limit frequency reached
12: Ready for running
13: Pre-exciting
14: Overload pre-alarm
15: Underload pre-alarm
16: Simple PLC stage completed
17: Simple PLC cycle completed
18: Set counting value reached
19: Designated counting value reached
20: External fault is valid
21: Reserved
22: Running time reached
23: Modbus/Modbus TCP communication
virtual terminal output
24:
PROFIBUS/CANopen/DeviceNET
communication virtual terminal output
25:
Ethernet
communication
-170-
Function parameter list
Default Modify
0
0
0
1
5