Kruger Ecowatt K320 Series Operation Manual page 207

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Multi-step time
P10.37
unit
P11 group––Protection parameters
Function
Name
code
Phase-loss
P11.00
protection
Frequency drop at
P11.01
transient
power-off
Energy braking for
P11.02
stop
Overvoltage stall
P11.03
protection
Description
run from the first step after restart.
1:
Continue
running
frequency when interruption occurred,
namely if the VFD stops during running
(caused by stop command or fault), it will
record the running time of current step,
and enters this step automatically after
restart, then continue running at the
frequency defined by this step in the
remaining time.
0: second; the running time of each step is
counted in seconds;
1: minute; the running time of each step is
counted in minutes
Description
0x000–0x111
Ones place:
0: Disable software input phase loss
protection
1: Enable software input phase loss
protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place:
0: Disable hardware input phase loss
protection
1: Enable hardware input phase loss
protection
0: Disable
1: Enable
0: Enable
1: Disable
0: Disable
1: Enable
-198-
Function parameter list
Default Modify
from
the
step
Default Modify
0
0x110
0
0
1