Kruger Ecowatt K320 Series Operation Manual page 296

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
RTU slave response (sent from the VFD to the master)
MSB of data writing address
LSB of data writing address
MSB of data quantity
LSB of data quantity
LSB of CRC
MSB of CRC
9.4.5 Data address definition
This section describes the address definition of communication data. The addresses are used
for controlling the running, obtaining the status information, and setting function parameters
of the VFD.
9.4.5.1 Function code address format rules
The address of a function code consists of two bytes, with the high-order bit on the left and
low-order bit on the right. The high-order bit ranges from 00 to ffH, and the low-order bit also
ranges from 00 to ffH. The high-order bit is the hexadecimal form of the group number before
the dot mark, and low-order bit is that of the number behind the dot mark. Take P05.06 as an
example: The group number is 05, that is, the high-order bit of the parameter address is the
hexadecimal form of 05; and the number behind the dot mark is 06, that is, the low-order bit is
the hexadecimal form of 06. Therefore, the function code address is 0506H in the hexadecimal
form. For example, the parameter address ofP10.01 is 0A01H.
Function
code
P10.00
Simple PLC mode
Simple PLC
P10.01
memory selection
Note:
The parameters in the P99 group are set by the manufacturer and cannot be read or
modified. Some parameters cannot be modified when the VFD is running; some cannot
be modified regardless of the VFD status. Pay attention to the setting range, unit, and
description of a parameter when modifying it.
START
ADDR
CMD
END
Name
0: Stop after running once
1: Keep running with the final value
after running once
2: Cyclic running
0: Without memory after power-off
1: With memory after power-off
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 (transmission time of 3.5 bytes)
Description
-287-
Communication
02H
10H
00H
04H
00H
02H
C5H
6EH
Default
Modify
0
0