Kruger Ecowatt K320 Series Operation Manual page 191

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Running
P08.06
frequency of jog
P08.07
ACC time for jog
P08.08
DEC time for jog
P08.09
Jump frequency 1 When the set frequency is within the
Jump frequency
P08.10
amplitude 1
P08.11
Jump frequency 2
Jump frequency
P08.12
amplitude 2
P08.13
Jump frequency 3
Jump frequency
P08.14
amplitude 3
Amplitude of
wobbling
P08.15
frequency
Amplitude of
P08.16
sudden jump
frequency
Description
The function code is used to define the
reference frequency during jogging.
Setting
range:
0.00Hz–P00.03
output frequency)
ACC time for jogging means the time
needed for the VFD to accelerate from
0Hz to the max. output frequency
(P00.03).
DEC time for jogging means the time
needed for the VFD to decelerate from
the max. output frequency (P00.03) to
0Hz.
Setting range: 0.0–3600.0s
range of jump frequency, the VFD runs
at the boundary of jump frequency.
The
VFD
can
resonance
points
frequencies. The VFD supports the
setting of three jump frequencies. If the
jump frequency points are set to 0, this
function is invalid.
Set frequency f
Jump
frequency 3
Jump
frequency 2
Jump
frequency 1
Setting
range:
0.00Hz–P00.03
output frequency)
0.0–100.0% (of the set frequency)
0.0–50.0% (of the amplitude of wobbling
frequency)
-182-
(Max.
avoid
mechanical
by
setting
jump
1/2* jump amplitude 3
1/2* jump amplitude 3
1/2* jump amplitude 2
1/2* jump amplitude 2
1/2* jump amplitude 1
1/2* jump amplitude 1
Time t
(Max.
Function parameter list
Default
Modify
5.00Hz
Model
depended
Model
depended
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.0%
0.0%