Kruger Ecowatt K320 Series Operation Manual page 74

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
code
Torque boost of
P04.01
Torque boost
P04.02
cut-off of motor 1
V/F frequency
P04.03
point 1 of motor 1
V/F voltage point
P04.04
1 of motor 1
V/F frequency
P04.05
point 2 of motor 1
V/F voltage point
P04.06
2 of motor 1
V/F frequency
P04.07
point 3 of motor 1
V/F voltage point
P04.08
3 of motor 1
compensation
P04.09
gain of motor 1
Low-frequency
oscillation control
P04.10
factor of motor 1
High-frequency
oscillation control
P04.11
factor of motor 1
Oscillation
control threshold
P04.12
of motor 1
V/F curve setting
P04.13
of motor 2
Torque boost of
P04.14
Torque boost
P04.15
cut-off of motor 2
V/F frequency
P04.16
point 1 of motor 2
Name
0.0%: (automatic); 0.1%–10.0%
motor 1
0.0%–50.0% (of the rated frequency of motor 1)
0.00Hz–P04.05
0.0%–110.0%
P04.03– P04.07
0.0%–110.0%
P04.05– P02.02 or P04.05– P02.16
0.0%–110.0%
V/F slip
0.0–200.0%
0–100
0–100
0.00Hz–P00.03 (Max. output frequency)
0: Straight-line V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customized V/F curve (V/F separation)
0.0%: (automatic); 0.1%–10.0%
motor 2
0.0%–50.0%(of the rated frequency of motor 1)
0.00Hz–P04.18
Description
-65-
Basic operation guidelines
Default
0.0%
20.0%
0.00Hz
0.0%
0.00Hz
0.0%
0.00Hz
0.0%
100.0%
10
10
30.00Hz
0
0.0%
20.0%
0.00Hz

Advertisement

Table of Contents
loading

Table of Contents