Kruger Ecowatt K320 Series Operation Manual page 322

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Category
PS1—COM
PS2—COM
PS3—COM
PS4—COM
PS5—COM
Digital
input/output
PS6—COM
PY1—CME
PY2—CME
Analog
input/output
PRO1A
PRO1B
PRO1C
Relay output
PRO2A
PRO2C
For details about the operation of programmable expansion cards, see the
Programmable Expansion Card Operation Manual
Sign
Name
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Digital output 1
Digital output 2
AI1
Analog input 1
AO1
Analog output 1
NO contact of relay 1
NC contact of relay 1
Common contact of
relay 1
NO contact of relay 2
Common contact of
relay 2
1. Internal impedance: 4 kΩ
2. Allowable voltage input: 12–30 V
3. Bidirectional terminal
4. Max. input frequency: 1 kHz
5. Supporting both source type input and
sink type input, but the input type must be
the same
1. Switch capacity: 200 mA/30 V
2. Output frequency range: 0–1 kHz
3. The terminals CME and COM are
shorted through J1 before delivery.
1. Input range: 0—10V or 0—20mA
2. Input resistance: 20kΩ for voltage input,
and 250kΩ for current input
3. Whether the input is the voltage or
current type is set through the jumper.
4. Resolution: When 10V corresponds to
50Hz, the min. resolution is 5mV.
5. Deviation ±1%, 25°C, full measuring
range
1. Output range: 0~10V voltage or 0—20mA
current
2. Whether the output is the voltage or
current type is set through the jumper.
3. Deviation ±1%, 25°C, full measuring
range
1. Contact capacity: 3A/AC 250 V, 1 A/DC
30 V
2. Do not use them as high-frequency
digital outputs.
.
-313-
Expansion cards
Function
Auto Station

Advertisement

Table of Contents
loading

Table of Contents