Ecowatt
Drive K320 series
®
Function
Name
code
P05.07
Reserved
Input terminal
P05.08
polarity
Digital input filter
P05.09
time
Virtual terminal
P05.10
setting
Terminal control
P05.11
mode
Description
72: Switch to the slave
73: Trigger fire mode control
74–79: Reserved
The function code is used to set the
polarity of input terminals.
When a bit is 0, the input terminal is
positive; when a bit is 1, the input terminal
is negative.
0x000–0x3F
The function code is used to set the filter
time for S1–S4, HDIA, and HDIB. In strong
interference cases, increase the value to
avoid maloperation.
0.000–1.000s
0x000–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT5: HDIB virtual terminal
The function code is used to set the mode
of terminal control.
0: Two-wire control 1, the enabling
consistent with the direction. This mode is
widely
used.
The
terminal command determines the motor
rotation direction.
FWD
K1
REV
K2
COM
1: Two-wire control 2, the enabling
separated from the direction. In this mode,
FWD is the enabling
direction depends on the defined REV
state.
-164-
Function parameter list
defined
FWD/REV
Running
FWD
REV
command
OFF
OFF
Stop
Forward
ON
OFF
running
Reverse
OFF
ON
running
ON
ON
Hold
terminal. The
Default Modify
0x000
0.010s
0x00
0