Kruger Ecowatt K320 Series Operation Manual page 176

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
P05.12 S1 switch-on delay
P05.13 S1 switch-off delay
S2 switch-on
P05.14
delay
S2 switch-off
P05.15
delay
S3 switch-on
P05.16
delay
S3 switch-off
P05.17
delay
S4 switch-on
P05.18
delay
S4 switch-off
P05.19
delay
HDIA switch-on
P05.20
delay
HDIA switch-off
P05.21
delay
HDIB switch-on
P05.22
delay
HDIB switch-off
P05.23
delay
P05.24
AI1 lower limit
Corresponding
P05.25
setting of AI1
lower limit
P05.26
AI1 upper limit
Corresponding
P05.27
setting of AI1
upper limit
AI1 input filter
P05.28
time
P05.29
AI2 lower limit
Corresponding
P05.30
setting of AI2
lower limit
Description
The function codes specify the delay time
corresponding
to
changes when the programmable input
terminals switch on or switch off.
Si Electrical
level
Invalid
Si Valid
Switch-on delay
Setting range: 0.000–50.000s
Note: After a virtual terminal is enabled,
the state of the terminal can be changed
only
in
communication
communication address is 0x200A.
The function codes define the relationship
between the analog input voltage and its
corresponding setting. When the analog
input voltage exceeds the range from the
upper limit to the lower limit, the upper
limit or lower limit is used.
When the analog input is current input,
0mA–20mA
current
0V–10V voltage.
In different applications, 100.0% of the
analog setting corresponds to different
nominal values. See the descriptions of
each application section for details.
The following figure illustrates the cases
of several settings:
-167-
the
electrical
level
Invalid
Valid
Switch-off delay
mode.
The
corresponds
Function parameter list
Default Modify
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.00V
0.0%
10.00V
100.0%
to
0.030s
-10.00V
-100.0%

Advertisement