Ecowatt
Drive K320 series
®
P05.08 (input terminal polarity)
0
S1
1 -1
0
S2
1 -1
0
S3
1 -1
0
S4
1 -1
P05.00
(HDI input type)
0
HDIA
1 -1
0
0
1
HD1B
1 -1
Note: Two different multifunction input terminals cannot be set as the same function.
Setting
Function
0
No function
1
Run forward (FWD)
2
Run reversely (REV)
Three-wire running
3
4
Jog forward
5
Jog reversely
6
Coast to stop
7
Fault reset
8
Pause running
9
External fault input
P05.09 (digital filter time)
P05.12
T delay
P05.14
T delay
P05.16
T delay
P05.18
T delay
P05.20
T delay
P05.22
T delay
The VFD does not act even if there is signal input. Set
unused terminals without functions to avoid misaction.
Control the forward/reverse running of the VFD by
external terminals.
Set the VFD running mode to 3-wire control mode by
control
this terminal. See P05.13 for details.
For details about the frequency and ACC/DEC time at
jogging, see P08.06, P08.07 and P08.08.
The VFD blocks output, and the stop process of motor is
uncontrolled by the VFD. This mode is applied in cases
of large-inertia load and free stop time; its definition is
the same as P01.08, and it is mainly used in remote
control.
External fault reset function, same as the reset function
of the STOP/RST key on the keypad. You can use this
function to reset faults remotely.
When the VFD decelerates to stop, however, all the
running parameters are in memory state, including PLC
parameter, wobbling frequency, and PID parameter.
After this signal disappears, the VFD restores to the
state before stop.
When an external fault signal is transmitted to the VFD,
the VFD releases a fault alarm and stops.
Digital function selection
P05.13
P05.01
T delay
(Default value is 1)
P05.15
T delay
P05.02
(Default value is 4)
P05.17
T delay
P05.03
(Default value is 7)
P05.19
T delay
P05.04
(Default value is 0)
P05.21
T delay
P05.05
(Default value is 0)
P05.23
T delay
P05.06
(Default value is 0)
Description
-95-
Basic operation guidelines
0
1
2
3
Run
4
Fault?
5
Fault
.
.
.
.
29
30
P17.11
Digital input
terminal state
P07.39
Input terminal
state of present
fault