P02 Group Motor 1 Parameters - Kruger Ecowatt Drive K120 Series Operation Manual

Table of Contents

Advertisement

Ecowatt
®
Drive K120 series
Function
Name
code
Restart
P01.21
after
power-off
Wait time
for restart
P01.22
after
power-off
P01.23 Start delay
Stop speed
P01.24
delay
0Hz
P01.25
output
selection

P02 group Motor 1 parameters

Function
Name
code
Type of
P02.00
motor 1
Description
The function code indicates whether the
VFD automatically runs after re-power on.
0: Disable
1: Enable. If the restart condition is met, the
VFD will run automatically after waiting the
time defined by P01.22.
The function code indicates the wait time
before the automatic running of the VFD that
is re-powered on.
Output frequency f
Running Power off
Setting range: 0.0–3600.0s (valid when
P01.21=1)
After a VFD running command is given, the
VFD is in standby state and restarts with the
delay defined by P01.23 to implement brake
release.
Setting range: 0.0–60.0s
Setting range: 0.0–100.0s
The function code is used to select the 0Hz
output of the VFD.
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for
stop
Description
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
t1=P01.22
t2=P01.23
t1
t2
Time t
Running
Power on
-44-
Function parameter list
Default
Modify
0
1.0s
0.0s
0.0s
0
Default
Modify
0