Ecowatt
Drive K320 series
®
Function
code
P08.43
UP/DOWN terminal
P08.44
Frequency increment
P08.45
change rate of the UP
Frequency decrement
P08.46
change rate of the DOWN
P17.00
P17.02
P17.14
Digital adjustment value 0.00Hz–P00.03
Name
Reserved
control setting
terminal
terminal
Set frequency
Ramp reference
frequency
Description
0x000–0x221
Ones place: Frequency setting selection
0: The setting made through UP/DOWN
is valid.
1: The setting made through UP/DOWN
is invalid.
Ones place: Frequency control selection
0: Valid only when P00.06=0 or
P00.07=0
1: Valid for all frequency setting
methods
2: Invalid for multi-step speed running
when multi-step speed running has the
priority
Hundreds place: Action selection for
stop
0: Setting is valid.
1: Valid during running, cleared after
stop
2: Valid during running, cleared after a
stop command is received
0.01–50.00 Hz/s
0.01–50.00 Hz/s
0.00Hz–P00.03 (Max. output frequency)
0.00Hz–P00.03 (Max. output frequency)
-87-
Basic operation guidelines
Default
0x000
0.50 Hz/s
0.50 Hz/s
0.00Hz
0.00Hz
0.00Hz