Kruger Ecowatt K320 Series Operation Manual page 218

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Communication
P14.01
baud rate
P14.02
Data bit check
Communication
P14.03
response delay
Description
The function code is used to set the data
transmission speed between upper
computer and the VFD.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note: The baud rate set on the VFD must
be consistent with that on the upper
computer. Otherwise, the communication
fails. A greater baud rate indicates faster
communication.
The data format set on the VFD must be
consistent
with
computer. Otherwise, the communication
fails.
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
0–200ms
The
function
communication response delay, that is, the
interval from when the VFD completes
receiving data to when it sends response
data to the upper computer. If the response
delay is shorter than the VFD processing
time, the VFD sends response data to the
upper computer after processing data. If
the
delay
is
longer
processing time, the VFD does not send
response data to the upper computer until
the delay is reached although data has
been processed.
-209-
that
on
the
upper
code
indicates
than
the
Function parameter list
Default Modify
4
1
the
5
VFD