Input/Output Signal Connection Diagram - Kruger Ecowatt K320 Series Operation Manual

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Terminal
name
S1
Digital input 1
S2
Digital input 2
S3
Digital input 3
S4
Digital input 4
Besides S1–S4 functions, the terminals can also act as high frequency
HDIA
pulse input channels
Max. input frequency: 50kHz;
Duty ratio: 30%–70%;
HDIB
Supporting
speed-measurement function
+24V—H1 STO input 1
+24V—H2 STO input 2

4.4.2 Input/output signal connection diagram

You can select the NPN/PNP mode and internal/external power through the U-type short
connector. NPN internal mode is adopted by default.
Internal impedance: 3.3kΩ
Accept 12–30V voltage input
Bi-directional
connection modes
Max. input frequency: 1kHz
All are programmable digital input terminals, the
functions of which be set through function codes
24V-power
Safe torque off (STO) redundant input, connected to the
external NC contact. When the contact opens, STO acts
and the VFD stops output;
Safety input signal wires use shielded wires whose length
is within 25m;
The H1 and H2 terminals are short connected to +24V by
default. Remove the short connectors from the terminals
before using STO function.
R01AR02A
R01BR02B
R01CR02C
U-type short-
U-type short-
contact tag of H1
contact tag of H2
and +24V
and +24V
Figure 4-16 Position of U-type short connector
Description
input
terminal,
quadrature
encoder
S1
S2
S3
S4 HDIA HDIB AI1 AI2 +10V
H1 +24V
+24V
PW COM HDO Y1 AO1 GND
PE
H2
+24V
COM COM
CME
485+
485-485G
U-type short-
U-type short-contact
contact tag of
tag of COM and
+24V and PW
-27-
Installation guidelines
supporting
NPN/PNP
input;
equipped
USB port Keypad port
+CME
with