Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
Communication
®
First, set the serial port to COM1. Then, set the baud rate consistently with P14.01. The data bits,
check bits, and end bits must be set consistently with P14.02. If the RTU mode is selected, you
need to select the hexadecimal form Input HEX. To set the software to automatically execute
the CRC function, you need to select ModbusRTU, select CRC16 (MODBU SRTU), and set the
start byte to 1. After the auto CRC check function is enabled, do not enter CRC information in
commands. Otherwise, command errors may occur due to repeated CRC check.
The commissioning command to set the VFD whose address is 03H to be forward running is
as follows:
03
06
20 00
00 01
42 28
VFD
Parameter
Write
CRC
Forward running
address
address
command
Note:
Set the address (P14.00) of the VFD to 03.
Set "Channel of running commands" (P00.01) to "Communication", and set "Communication
channel of running commands" (P00.02) to the Modbus communication channel.
Click Send. If the line configuration and settings are correct, a response transmitted by the
VFD is received as follows:
03
06
20 00
00 01
42 28
VFD
Parameter
Write
CRC
Forward running
address
address
command