Kruger Ecowatt K320 Series Operation Manual page 75

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
code
V/F voltage point
P04.17
1 of motor 2
V/F frequency
P04.18
point 2 of motor 2
V/F voltage point
P04.19
2 of motor 2
V/F frequency
P04.20
point 3 of motor 2
V/F voltage point
P04.21
3 of motor 2
compensation
P04.22
gain of motor 2
Low-frequency
oscillation control
P04.23
factor of motor 2
High-frequency
oscillation control
P04.24
factor of motor 2
Oscillation
control threshold
P04.25
of motor 2
Energy-saving
P04.26
Voltage setting
P04.27
Name
0.0%–110.0%
P04.16– P04.20
0.0%–110.0%
P04.18– P02.02 or P04.18– P02.16
0.0%–110.0%
V/F slip
0.0–200.0%
0–100
0–100
0.00Hz–P00.03 (Max. output frequency)
0: Disable
run
1: Automatic energy-saving run
0: Keypad; Output voltage is determined by
P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step running
6: PID
7: Modbus/Modbus TCP communication
channel
8:
communication
9: Ethernet communication
10: HDIB
11:
communication
12: Programmable expansion card
13: Reserved
Description
Profibus/CANopen/DeviceNet
EtherCat/Profinet/EtherNetIP
-66-
Basic operation guidelines
Default
0.0%
0.00Hz
0.0%
0.00Hz
0.0%
100.0%
10
10
30.00Hz
0
0

Advertisement

Table of Contents
loading

Table of Contents